ODC Logo

 

GT SYSTEM 1200 MANUAL SLIDER
I.C.U./CC.U
TRACKLESS MODEL
Suggested Architectural Specifications
SECTION 8
MANUAL ENTRANCE SYSTEMS

PART 1-GENERAL

1.01  DESCRIPTION

 

 

A.              Furnish and install door equipment as indicated on drawings and specifications.

B.              Related work specified elsewhere.

 

1.     Prepared Opening: Section

 

2.     Glazing: Section _______

 

 

 

1.02 QUALITY ASSURANCE

 

 

A.              Manufacturer's Qualifications:


Products specified shall be represented by a factory authorized and trained distributor. Distributor shall maintain a parts inventory and trained personnel capable of providing service.

 

 

1.03 SUBMITTALS

 

 

A.        Shop drawings showing complete elevations, details and method of anchorage to location; installation of hardware; size, shape and thickness of materials; joints and connections; and details of joining with other construction.

 

B.              Templates and diagrams and/or shop drawings as needed shall be furnished to fabricators and installers of related work for coordination of doors, frames, hardware, concrete work and other work.

 

C.        A copy of appropriate maintenance manual shall be provided to owner’s engineer upon completion of installation.

 

 

1.04 WARRANTY

 

 

A.        Warrant all material and labor provided by automatic door equipment installer against defects in material and workmanship at no cost to owner, for a period of one year from date of substantial completion. Provide warranty to owner after completion of installation.

 

PART 2-PRODUCTS

2.01 APPROVED MANUFACTURER

 

A.             All door equipment shall be distributed by:


Ontario Door Controls

1350 Matheson Boulevard East

Unit 16, Mississauga

Ontario, Canada.

Phone: (905) 238 9222

Fax    : (905) 238 9279

e-mail: products@automaticdoorsystems.com

 

Website: http://www.automaticdoorsystems.com

 

 

2.02 MANUAL SLIDING DOOR SYSTEM

 

GYRO Slide System 1200

 

A.        Mode of Operation: The GYRO TECH Series 1200 Intensive Care (I.C.U.)/Cardiac Care Unit (I.C.U.) package provides the unique feature of room access without a floor track. Smooth entry and exit is provided for patient and also for delicate medical equipment. This feature also precludes the chance of contaminant build up. Under normal operating conditions, medical personnel have access by way of the sliding door. When patient and/or medical equipment access is required, the sliding door is moved to the breakaway position capturing the transfer pivot. At this location, the door and swing panel becomes a pivoting unit and can swing 90 degrees giving access to approximately 95% of the framed opening. Reset procedures occur in reverse order.

 

B.             Product Components:

 

1.     Aluminum doors, swing panels and frame assembly.

2.     Rollers - Support and Guide.

3.     Door carrier hanger assembly, swing panel pivots, breakaway latches, limiting arms, pull handles, static arrester, and weathering seal.

1a)       Door panel and Swing panel shall be factory assembled with 3/8-16 threaded tie rods spanning full length of top and bottom rails. Snap in glass stop with integral extruded vinyl standoff to accommodate glass flexing. A horizontal muntin bar to provide glass protection.

 

1b)       Vertical Jambs and Horizontal Header shall be 1-3/4 x 4-1/2" (44.4 mm x 114.3 mm) extruded aluminum tubes. High strength KB-45 aluminum roller track shall be mounted and fastened inside the header and shall be replaceable in the event of damage.

 

1c)       All major extrusions to be minimum .125 (3.2 mm) wall thickness.

 

1d)       All extruded aluminum sections shall be 6063-T5 or equivalent.

 

1e)       Finish: Aluminum shall have a standard finish of AA-M12-C22-A41 (204 R1) or AA-M12-C22-A4

(dark bronze). Black and special finishes available upon request

3.         Sliding door suspension provided by two, three wheeled nylon roller assemblies rated at 200 lbs. each. Each roller assembly shall have + 1/8" (3.l8mm) of vertical adjustment. Each swing panel shall include one spring-loaded bottom guide roller assembly, incorporating a rubber outer shell and lubricated sealed ball bearing. Guide roller shall be attached to the swing panel with a 1/4" (6.35 mm) thick-formed guide bracket. All steel brackets and fitting shall be plated for corrosion resistance.

           

3a)       Entrance systems shall have door panels attached to a door carrier hanger assembly by means of an adjustable support rod pivot assembly and corrosion resistant adjustable breakaway release latch holding the door panel in the closed position under normal manual operation. The support rod pivot assembly allows door to swing freely in panic mode without sagging. The system shall have breakaway swing panels held in place by means of a top pivot and floor pivot plate secured to the floor and a corrosion resistant adjustable breakaway release latch for holding the panel in the closed position. Breakaway pressure shall be field adjustable (5-50 lbs.) to meet local building code requirements but will be factory set at 50 lbs. maximum.

 

3b)       All panels shall have a limiting arm to control the panel swing in the direction of egress.

 

3c)       Door pull adjacent to swing panel is of recessed type to preclude pinch point. External door activation is provided by a pull handle.

 

3d)       An electrical grounding system on each door grounds entrance package from static electricity.

 

3e)       15/16" wide vinyl strip seal positioned between the door(s) and lead stile(s) of the swing panel(s).

 

 

PART 3-EXECUTION

3.01 INSTALLATION

 

Door equipment shall be installed by manufacturer-approved, factory -trained installers in compliance with manufacturer's recommendations and approved shop drawings.

 

 

3.02 CLEANING AND PROTECTION

 

After installation, clean framing members as recommended by manufacturer. Aluminum surfaces in contact with masonry, concrete, or steel shall be protected by use of neoprene gaskets where indicated or a coat of bituminous paint to prevent galvanic or corrosive action. Advise general contractor to protect unit from damage during subsequent construction activities.

 

 

*COVER NOTE TO SPECIFICATION WRITER

 

A.    Preparation of a plumb and square opening to receive sliding door equipment with adequate support.

 

B.    Glass and glazing shall be described in glazing section of the specifications.

 

 
Back to Gyro Tech System 1200 description Return to ODC home page
Please contact us at products@automaticdoorsystems.com